| Hidros GHE FC (Ichiil 200) Registerlist |
| Hidros GHE FC (Ichill 200) Datasheet |
| Hidros GHE FC (Ichill 200) Manual |
| Hidros GHE FC (Ichill 200) Betriebshandbuch |
| INDEX | NAME | DIRECTION | REGISTER | COUNT | FUNCTION | TYP | CONVERTION | ENUMS | UNIT |
|---|---|---|---|---|---|---|---|---|---|
| 0 | mode_status | READ & WRITE | 1280 | 1 | fc3/fc16 | bool | reading: 0=stand-by/remote-off, 1=chiller mode/heat pump mode, writing only power off | ||
| 1 | on/off_status | READ | 1280 | 1 | fc4 | bool | 1: on mode, 0: remote off | ||
| 2 | chiller_status | READ & WRITE | 1280 | 1 | fc3/fc16 | bool | reading: 0=chiller off, 1= chiller on, writing: 1=chiller on | ||
| 3 | heat_pump_status | READ & WRITE | 1280 | 1 | fc3/fc16 | bool | reading: 0= heat pump off, 1= heat pump on, writing: 1= heat pump on | ||
| 4 | buzzer_status | READ & WRITE | 1280 | 1 | fc3/fc16 | bool | 1= stop buzzer | ||
| 5 | dinamic_set_point | READ | 1280 | 1 | fc4 | bool | 1= set point active | ||
| 6 | energy_saving_mode | READ & WRITE | 1280 | 1 | fc3/fc16 | bool | 1= energy saving mode active |