| INDEX | NAME | DIRECTION | REGISTER | COUNT | FUNCTION | TYP | CONVERTION | ENUMS | UNIT |
|---|---|---|---|---|---|---|---|---|---|
| 0 | charge_point_power | READ | 400 | 1 | fc4 | ui32 | W | ||
| 1 | charge_point_state | READ | 1000 | 1 | fc4 | ui16 | "0: ""Available"", 1: ""Preparing"", 2: ""Charging"", 3: ""SuspendedEVSE"", 4: ""SuspendedEV"", 5: ""Finishing"", 6: ""Reserved"", 7: ""Unavailable"", 8: ""Faulted""," | ||
| 2 | cable_state | READ | 1004 | 1 | fc4 | ui16 | 0: Cable not connected, 1: Cable connected, vehicle not connected, 2: Cable connected, vehicle connected, 3: Cable connected, vehicle connected, cable locked | ||
| 3 | EVSE_fault_code | READ | 1006 | 1 | fc4 | ui32 | 0: No fault, Other: Fault code | ||
| 4 | current_l1 | READ | 1008 | 1 | fc4 | ui16 | mA | ||
| 5 | current_l2 | READ | 1010 | 1 | fc4 | ui16 | mA | ||
| 6 | current_l3 | READ | 1012 | 1 | fc4 | ui16 | mA | ||
| 7 | voltage_l1 | READ | 1014 | 1 | fc4 | ui16 | V | ||
| 8 | voltage_l2 | READ | 1016 | 1 | fc4 | ui16 | V | ||
| 9 | voltage_l3 | READ | 1018 | 1 | fc4 | ui16 | V | ||
| 10 | active_power_total | READ | 1020 | 1 | fc4 | ui32 | W | ||
| 11 | meter_reading | READ | 1036 | 1 | fc4 | ui32 | x/10 | kWh | |
| 12 | failsafe_timeout | READ & WRITE | 2002 | 1 | fc3/fc16 | ui16 | s | ||
| 13 | charging_current | READ & WRITE | 5004 | 1 | fc3/fc16 | ui16 | A | ||
| 14 | alive_register | READ & WRITE | 6000 | 1 | fc3/fc16 | ui16 | EMS (Master) writes 1 EVSE (Slave) writes 0 (EVSE checks this register at a period of (Failsafe Timeout)/2 for a value of 1, and sets it to 0. Period cannot go less than 3 seconds) |