INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 flow READ 0 2 fc4 int32 x/10 l/h
1 temp_internal READ 2 1 fc4 int16 x/100 °C
2 temp_remote READ 3 1 fc4 int16 x/100 °C
3 temp_difference READ 4 1 fc4 int16 x/100 °C
4 pressure READ 5 1 fc4 int16 x/1000 bar
5 power READ 6 2 fc4 int32 x/100 kW
6 air_bubble_signal READ 10 1 fc4 ui16 0: no air 1: air detected
7 bubble_detection READ 11 1 fc4 ui16 0: no air 1: small amount of air 2: medium amount of air 3: high amount of air
8 energy_sum READ 506 2 fc4 int32 x/100 kWh