DEVICE DB Impressum & Datenschutz

General parameter

General Modbus-parameter

Description (HTML)


Note


Documents

Belimo Flow sensor datasheet
Belimo Flow sensor registerlist

Device Image (JPEG)

No image uploaded.

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 relative_volumatric_flow READ 7 6 fc3 ui16 x/100 %
1 absolute_volumatric_flow READ d0 ui16 x/100 l/s
2 absolute_volumatric_flow_in_selected_units_lowword READ d0 ui16 x/1000 UnitSel
3 sensor_value_1 READ d0 ui16 mV|0/1
4 temperature READ 22 2 fc3 ui16 x/100 °C
5 glycol_cincentration READ 26 1 fc3 ui16 x/100 %
6 total_volume READ 60 6 fc3 ui16 x/100
7 total_volume_in_selected_units_lowword READ d9 ui16 UnitSel
8 total_volume_in_selected_units_highword READ d9 ui16 UnitSel
9 bus_termination READ 100 5 fc3 ui16 0/1 disabled/enabled
10 series_number_1st_part READ d15 ui16
11 series_number_2nd_part READ d15 ui16
12 series_number_4th_part READ d15 ui16
13 malfunction_and_service_information READ d15 ui16 0/1/2/3/4/5/6/7/8/9/10/11/12 :-/-/-/reverse flow/-/-/flow actual exceeds fs/flow measurement error/-/flowbody temperature error/communication to sensor interrupted/freeze warning/glycol detected
14 fs(full_scale,max_flow) READ 111 3 fc3 ui16 x/100 l/s
15 fs(full_scale,max_flow)_in_selected_unit_lowword READ d20 ui16 x/1000 UnitSel
16 fs(full_scale,max_flow)_in_selected_unit_highword READ d20 ui16 x/1000 UnitSel
17 sensor_1_typ READ & WRITE 121 1 fc3/fc16 ui16 0/1/2/3/4 none/active/-/-/switch
18 unit_selection_flow READ & WRITE 148 1 fc3/fc16 ui16 0/1/2/3/4/5/6 m³/s|m³/h|l/s|l/min|l/h|gpm|cfm
19 unit_selection_volume READ & WRITE 150 1 fc3/fc16 ui16 0/1/2/3 m³/litre/gallon/cf