SolaX Power X1 Hybrid Inverter Registerlist

Device Image (JPEG)

No image uploaded.

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 grid_voltage READ 30000 1 fc4 ui16 x/10 V
1 grid_current READ 30001 1 fc4 int16 x/10 A
2 grid_power READ 30002 1 fc4 int16 x/1000 kW
3 grid_frequency READ 30007 1 fc4 ui16 x/100 Hz
4 radiator_temperature READ 30008 1 fc4 int16 °C
5 run_mode READ 30009 1 fc4 ui16 0: waiting, 1: checking, 2: normal, 3: fault, 4: permanent fault, 5: update, 6: off-grid waiting, 7: off-grid, 8: self testing, 9:idle, 10: standby
6 batvoltage_charge1 READ 30020 3 fc4 int16 x/10 V
7 batcurrent_charge1 READ d6 int16 x/10 A
8 batpower_charge1 READ d6 int16 x/1000 kW
9 BMS_connect_state READ 30023 1 fc4 ui16 0/1 0: disconnected, 1: connected
10 battery_capacity READ 30028 1 fc4 ui16 %
11 BMS_charging_maxcurrent READ 30036 3 fc4 ui16 x/10 A
12 BMS_discharging_maxcurrent READ d11 ui16 x/10 A
13 BMS_battery_capacity READ d11 ui16 x/1000 kW
14 feedin_power READ 30070 2 fc4 ui32 x/1000 kW (positive= generate power, negative= consume power)
15 feedin_energy_total READ 30072 2 fc4 ui32 x/100 kWh
16 consumed_energy_total READ 30074 2 fc4 ui32 x/100 kWh
17 energy_today READ 30080 1 fc4 ui16 x/10 kWh
18 energy_total READ 30082 1 fc4 ui32 x/10 kWh
19 lock_state READ 30084 1 fc4 ui16 0/1 0: locked, 1: unlocked
20 off-grid_voltage READ 30076 1 fc4 ui16 x/10 V
21 off-grid_current READ 30077 1 fc4 ui16 x/10 A
22 off-grid_power READ 30078 1 fc4 ui16 VA
23 off-grid_frequency READ 30079 1 fc4 ui16 x/100 Hz