| INDEX | NAME | DIRECTION | DEFAULT | UNIT | INFO |
|---|---|---|---|---|---|
| 0 | I.WorkingLevel | INPUT | 0 | off/level1/level2/level3/level4 | Current working level of the vent. enum[0=off,1=level1,2=level2,3=level3,4=level4] |
| 1 | I.DeviceModel | INPUT | 0 | standard/pluggit/zimmermann-proxonV1/westaflex/stiebelLWZ/zimmermann-proxonV2 | Current device model of the vent. enum[0=standard,1=pluggit,2=zimmerm/proxonV1,3=westaflex,4=stiebelLWZ,5=zimmerm/proxonV2] |
| 2 | I.WorkingMode | INPUT | 0 | zimmermann: off/ecoSummer/ecoWinter/comfort/stove proxon: auto/manual/pluggitAuto/pluggitWeek | Current working mode of the vent. Different device models may have different working modes. #zimmermann:enum[0=off,1=ecoSummer,2=ecoWinter,3=comfort,4=stove]#proxon:[0=auto,1=manual,2=pluggitAuto,3=pluggitWeek] |
| 3 | I.BypassState | INPUT | 0 | auto/manual/summer | How the air is redirecting. enum[0=auto,1=manual,2=summer] |
| 4 | I.MaximumWorkingLevel | INPUT | 0 | ||
| 5 | I.RelativeHumidityLevel | INPUT | 40 | % | Current relativity humidity of the vent measured by the internal sensor. float[0.00,100.00] |
| 6 | I.AirQualityLevel | INPUT | 50 | % | Current air quality level measured by the internal sensor of the vent. float[0.00,100.00] |
| 7 | I.CO2Value | INPUT | 100 | ppm | Current CO2 value measured by the internal sensor of the vent in parts per million (ppm). float[0.00,100000.00] |
| 8 | I.SupplyAirTemperatureValue | INPUT | 20 | °C | Current temperature value measured from the air supplied by the vent to the space (room, etc). float[-100.00,100.00] |
| 9 | I.ExhaustAirTemperatureValue | INPUT | 20 | °C | Current temperature value measured from the used air extracted back by the vent from the space (room, etc). float[-100.00,100.00] |
| 10 | I.OutsideAirTemperatureValue | INPUT | 20 | °C | Current temperature value measured from the outside air that the vent will take/process (source air). float[-100.00,100.00] |
| 11 | I.OutgoingAirTemperaturevalue | INPUT | 20 | °C | Current temperature value measured from the used air that will be put back outside (street, etc). float[-100.00,100.00] |
| 12 | I.SupplyAirWorkingLevel | INPUT | 0 | % | Percentage value of how much air the vent is blowing into the space. float[0.00,100.00] |
| 13 | I.ExhaustAirWorkingLevel | INPUT | 0 | % | Percentage value of how much air the vent is sucking from the space. float[0.00,100.00] |
| 14 | I.ElementInfo | INPUT | 0 | auto/manualOff/manualOn/locked/alarm | Information about the light element status inside myGEKKO OS. It shows the sumstate of the manual selection mode and alarms/locking state. enum[0=auto,1=manualOff,2=manualOn,3=locked,4=alarm] |
| 15 | I.SubWorkingMode | INPUT | 0 | zimmermann: middleTemp+offset1/onlyOffset others: exhaust-supply/exhaust-supply-heatRecovery | Current sub-working mode of the vent. Different device models may have different sub-working modes. #zimmermann:enum[0=middleTemp+offset,1=onlyOffset]#others:enum[0=exhaust,1=exhaust/supply,2=exhaust/supply/heatRecovery] |
| 16 | I.CoolingModeState | INPUT | 0 | off/on | Current state of the cooling option of the vent. If cooling mode is "off" it means that it is heating. enum[0=off,1=on] |
| 17 | I.DehumidModeState | INPUT | 0 | off/on | Current state of the dehumid option of the vent |
| 18 | I.BypassMode | INPUT | 0 | auto/manual/summer | enum[0=auto,1=manual,2=summer] |
| 19 | O.RequestGlobalStatus | OUTPUT | 0 | UPDATE | |
| 20 | O.RequestDiscovery | OUTPUT | 0 | DISCOVERY | |
| 21 | O.SetWorkingLevel | OUTPUT | 0 | off/level1/level2/level2/level3/level4 | Change the current working level of the vent. The range of values that will work would be [-1, maxWorkingLevel]. enum[-1=off,1=level1,2=level2,3=level3,4=level4] |
| 22 | O.ToggleWorkingLevel | OUTPUT | 0 | toggle | Toggle the current working level of the vent between off and the last working level. enum[1=toggle] |
| 23 | O.SetBypassMode | OUTPUT | 0 | auto/manual/summer | enum[0=auto,1=manual,2=summer] |
| 24 | O.SetCoolingModeState | OUTPUT | 0 | off/on | Change the current state of the cooling option of the vent. enum[0=off,1=on] |
| 25 | O.SetDehumidModeState | OUTPUT | 0 | off/on | Change the current state of the dehumid option of the vent. enum[0=off,1=on] |
| 26 | O.SetWorkingMode | OUTPUT | 0 | zimmermann: off/ecoSummer/ecoWinter/comfort/stove proxon: auto/manual/pluggitAuto/pluggitWeek | Change the current working mode of the vent. Different device models may have different working modes. #zimmermann:enum[0=off,1=ecoSummer,2=ecoWinter,3=comfort,4=stove]#proxon:[0=auto,1=manual,2=pluggitAuto,3=pluggitWeek] |