Downloads sind nur für aktive Benutzer (active > 0) verfügbar.
Der Zugriff auf DDF-Dateien ist nur für aktive Benutzer (active > 0) möglich.
| INDEX | NAME | DIRECTION | REGISTER | COUNT | FUNCTION | TYP | CONVERTION | ENUMS | UNIT |
|---|---|---|---|---|---|---|---|---|---|
| 0 | setpoint | READ & WRITE | 1 | 1 | fc3/fc16 | ui16 | x/100 | % | |
| 1 | override_control | READ & WRITE | 2 | 1 | fc3/fc16 | ui16 | 0/1/2/3/4/5 | none/open/close/min/mid/max | |
| 2 | command | READ & WRITE | 3 | 1 | fc3/fc16 | ui16 | 0/1/2/3/4 | none/adaption/test/sync/reset | |
| 3 | actuator_type | READ | 4 | 1 | fc3 | ui16 | 0/1/2/3/4/5 | actuator not connected/air,water/vav,epiv/fire/energy valve/6way epiv | |
| 4 | relative_position | READ | 5 | 5 | fc3 | ui16 | x/100 | % | |
| 5 | absolute_position | READ | d5 | ui16 | ° | ||||
| 6 | relative_volumatric_flow | READ | d5 | ui16 | x/100 | % | |||
| 7 | absolut_volumatric_flow | READ | d5 | ui16 | l/min | ||||
| 8 | sensor_1_value | READ | d5 | ui16 | mV|0/1 | ||||
| 9 | absulute_volumatric_flow_lowword | READ | 11 | 3 | fc3 | ui16 | x/1000 | UnitSel | |
| 10 | absulute_volumatric_flow_highword | READ | d9 | ui16 | x/1000 | UnitSel | |||
| 11 | setpoint_analog | READ | d9 | ui16 | x/100 | % | |||
| 12 | bus_termination | READ | 100 | 5 | fc3 | ui16 | 0/1 | inactive/active | |
| 13 | series_number_1st_part | READ | d12 | ui16 | |||||
| 14 | series_number_2nd_part | READ | d12 | ui16 | |||||
| 15 | series_number_4th_part | READ | d12 | ui16 | |||||
| 16 | malfunction_and_service_information | READ | d12 | ui16 | Bit1/Bit2/Bit8/Bit9/Bit10 | mech travel incresed/actuator cannot move/internal activity/gear disengaged/bus watchdog triggerd | |||
| 17 | sensor_1_typ | READ & WRITE | 108 | 1 | fc3/fc16 | ui16 | 0/1/2/3/4 | none/active,hybrid/-/-/switch | |
| 18 | bus_fail_position | READ & WRITE | 109 | 1 | fc3/fc16 | ui16 | 0/1/2/3 | none,last setpoint/fast close/fast open/mid position | |
| 19 | timeout_for_bus_watchdog_in_s | READ & WRITE | 110 | 1 | fc3/fc16 | ui16 | s | ||
| 20 | max/vmax | READ & WRITE | 107 | 1 | fc3/fc16 | ui16 | x/100 | % | |
| 21 | nominal_volumatric_flow | READ | 111 | 3 | fc3 | ui16 | l/min | ||
| 22 | nominal_volumatric_flow_lowword | READ | d21 | ui16 | x/1000 | UnitSel | |||
| 23 | nominal_volumatric_flow_highword | READ | d21 | ui16 | x/1000 | UnitSel | |||
| 24 | control_mode | READ & WRITE | 117 | 1 | fc3/fc16 | ui16 | 0/1 | position control/flow control | |
| 25 | unit_selection_flow | READ & WRITE | 118 | 1 | fc3/fc16 | ui16 | 0/1/2/3/4/5/6 | m³/s|m³/h|l/s|l/min|l/h|gpm|cfm | |
| 26 | setpint_source | READ & WRITE | 119 | 1 | fc3/fc16 | ui16 | 0/1 | analog/bus |